Multi-line 2 AGC 200 Application Software

Multi-line 2 AGC 200 Application Software

You have chosen to download our software.

Within a few seconds, you will receive an email containing a download link.

Having trouble using the software? Please contact support@deif.com. 

Best regards, 

DEIF A/S

The software is subject to copyright DEIF A/S
By following the above mentioned link and downloading the file you automatically accept DEIF A/S copyright and license agreement (EULA). The license agreement can be found on www.deif.com/software

4.68.5

PM compatibility version 1.16.1.
Includes version 1.02.0 + 1.15.2.

Corrections:

  • Corrected that PMS island load sharing and asymmetrical load sharing did not work correctly when #9030 Scaling was set to other than default.

4.68.5

13.07.2021

PM compatibility version 1.16.1.
Includes version 1.02.0 + 1.15.2.

Corrections:

  • Corrected that PMS island load sharing and asymmetrical load sharing did not work correctly when #9030 Scaling was set to other than default.

4.68.4

03.08.2020

PM compatibility version 1.16.1
Includes version 1.02.0 + 1.15.2

Corrections:

  •    Situations where multi start would not work correctly in island and AMF applications are corrected.
  •    In AMF situations where the mains had no TB and #7065 mains fail, ctrl was set to "Start engine" and the DGs had to connect through a BTB to supply the mains. The MB would not open because it did not have information about whether or not the DGs Hz/V OK timer had run out. The MB would not open and the BTB would not close, resulting in a deadlock. This has been corrected.

4.68.3

03.04.2020

PM compatibility version 1.16.1.
Includes version 1.02.0 + 1.15.2.

Corrections:

  •    Modbus interface is corrected due to receiving USW paramter files.

4.68.2

19.11.2019

PM compatibility: 1.16.1.
Includes versions: 1.02.0 & 1.15.2.

Corrections:

  • With German option V0108 in DG the TEST button can only activate TEST when the single plant contains a MAINS connection.
  • The display no longer freezes when a USB connection is activated. Bug introduced in version 4.68.1.

4.68.1

04.10.2019

PM compatibility: 1.16.1.
Includes versions: 1.02.0 & 1.15.2.

Corrections:

  • Parameters 7741 and 7743 are no longer overwritten with default values after a power-cycle.
  • TCP/IP connections are closed correctly when no longer in use.

4.68.0

09.01.2019

PM compatibility: 1.16.1.
Includes versions: 1.02.0 & 1.15.2.

New features:

  • Mains ATS functionality has been added. Can be activated when the mains is alone in an application with MB and TB. It can also be used in a power management application as a backup if the Power Management CAN fails.
  • 16 flip flops have been added to M-Logic.
  • 64 new virtual inputs have been added.
  • ASC-4 Battery is supported.
  • Free PID regulators have been added.
  • Easy Connect feature has been added. Enabled in menu 8023.
  • JCB live link support has been added. Enabled in menu 7552.
  • Various numbers of AC "average of all phases" alarms have been added. Menus 14000-14130 are only available via USW.
  • P current set point and cos phi current set point can now be used for transducer output in menu 5690+5710. Values are also available on Modbus.
  • If a busbar is black and a position fail happens, a new “busbar blocked” alarm will appear. New status texts will also inform which controller has a position failure that needs to be corrected.
  • A breaker can now be racked out.

Changes:

  • EIC DEF Temp has been added in delta analogue alarms.
  • Dynamic synchronisation minimum voltage parameter has been added (ch 2024) to ensure a certain level of voltage.
  • EIC RPM Overspeed (menu 7600) alarm has been added. This also makes shutdown during shutdown override.
  • MB and TB open inhibits have been added in M-Logic.

Corrections:

  • In an application with multiple mains controllers without tie breakers, entering block mode on one mains could cause another mains breaker to trip shortly. This is now corrected.
  • CIO is not working together with MDEC 302/303 and ADEC 501 protocols when present on the same CAN line.
  • A mains controller with no tie breaker will no longer trip its mains breaker when power cycled.
  • Engine Fuel Leakage 1 (SPN 1239) state has been added to M-Logic.

4.65.0

22.12.2017

PM compatibility: 1.16.0 Includes versions: 1.02.0 & 1.15.2.

New features:

  • Support of ALC-4
  • 32 DG/mains support
          • Support of 32 DGs, in ID range 1-32
          • Support of 32 mains, in ID range 1-32
          • Support of 16 ASCs, in ID range 25-40 (ASC version 4.06.0 required)
          • Support of  8 ALCs, in ID range 25-40 (ALC version 4.01.0 required)
          • New settings added for priority 17-32 in the menus 8106, 832x, 833x and 834x
          • Fuel optimisation logic simplified. Parameters in menu 8170 removed. LD start/stop timers used instead.
          • Fuel optimisation + Running hours mode added. (To even the usage of same-size gensets).
          • Load-dependent start/stop 2 enable settings added to display menus.
          • PMS M-Logic events added for new DG/mains IDs
          • New alarm added: "PMS protocol error". (Triggers if old software is present in a setup using DG IDs 17-32 or mains ID 1-16).
          • Note: Quick setup and Heavy consumer features are not supporting DG IDs 17-32 and mains ID 1-16.
  • Phase sequence error can now be emulated if emulation is active.

Changes:

  • EIC: Added PGN ETC3 to Caterpillar and Perkins protocols
  • EIC: Added TSC1 Checksum to Iveco protocol
  • EIC: Added CAN stop request Deutz EMR protocol

Corrections:

  • M-Logic version of "mains okay" command now works in the same way as the input "mains okay" command.
  • The input "mains okay" is now logged in both high and low states when it is configured either in M-Logic or through the IO list.
  • Corrected: Beckhoff digital outputs could flicker.
  • Power capacity improved to avoid overloading DGs in a setup with several TBs and a failing DG. Also, M-Logic command "TB power capacity - direct close" will now speed up AMF sequences where mains fail control is set to "Start engine".
  • Redundant DG only closes ground relay when changing to MASTER.
    Phase sequence error status texts could appear even if they should be inhibited. GB would not close because of phase sequence error even if it was inhibited.

4.60.0

21.11.2017

PM compatibility: 1.15.2
Includes versions: 1.02.0 & 1.15.1.

New features:

  • CBE: Voltage level detection for allowing rerun added.
  • EIC Winding temp. and DEF Level added to Delta analouge input alarms
  • CBE: Setup for excitation during cooldown added.
  • LED colours can now be changed. An option to select a different LED colour behavior. Parameter 6082
  • Deload sequence can now be changed to: "TB open before GB" and be enabled with parameter 8273 "Deload TB back sync."
  • Reverse power and overload alarms added for 4th CT measure input. Menu 7440-7450-7460-7474.
  • Built-in buzzer control via M-Logic added.
  • OFF button inhibit via M-Logic added.
  • Engine Communication and digital AVR is no longer required to be on the same CAN line.
  • EIC: Volvo Penta EMS 2 TIER 4 support.
  • EIC: Support of checksum in TSC1 telegram added for Volvo-Penta EMS 2.
  • EIC: Added support of CAN SENS battery charger.
  • EIC: EIC events have been mapped to Modbus.
  • Battery test extended and can be done with a start sequence. Battery test can now crank more times. 
  • New failclass "Controlled stop" added for securing the cooldown to be executed.
  • Warm up ramp after GB synchronised added. Holds the delivered power on the "stage 1" until a wished temperature is reached on a selected input.
  • EIC: MTU J1939 Smart Connect added support for CPC4 variant.
  • EIC: PSI (Power Solutions International) J1939 protocol added.
  • EIC: PGN64913 added to PSI protocol. This PGN transmits the status of the breaker feedbacks - both GB and MB.
  • EIC: Engine derate request added on all J1939 protocols.
  • Alarm 8291 "BB meas failure" has been introduced for DG units. This alarm checks if the DG controller can measure the busbar voltage. If not, it will check if the other DGs in the PMS system can. If they can, the DG will issue an alarm.
  • Selco T4800 is now available as analogue load-share device in menu 6390

Changes:

  • Password required when entering or leaving BLOCK mode.
  • In parameter #7806, the selection +-10  V has been removed. The new default selection is 0-10 V.
  • Parameter #7802 is no longer available.
  • Inhibit on Ext engine stop alarm available.
  • EIC: Added ambient temperature measurements to MTU ADEC protocol.
  • EIC: Volvo Penta EMS 2 support for DEF level to be read on different source addresses added.

Corrections:

  • When a mains is instructed to switch to a DG supply, it first checks if there is an available DG supply before opening the MB.
  • Improvements for breaker open point during power derate active.
  • MB is no longer opened in AUS mode when a mains failure occurs and modeshift is on.
  • Parameters 7741 and 7743 are now scaled properly in the USW according to parameter 9030. Furthermore, the minimum and maximum ranges for 7741 to 7744 have been changed.
  • Relay error occurs when setting alarm output to limit while using Beckhoff.
  • Transducer output with AC frequency measurement as input/reference is working again.

 

4.59.2

03.05.2017

PM compatibility: 1.15.2
Includes versions: 1.02.0 & 1.15.1.

Corrections:

  • Overlap time (two breakers in parallel: MB/GB or MB/TB) is now maximum of the timer set point in menu 2760.
  • Support of MAIN PCB version 4 added.

 

 

4.59.1

16.03.2017

PM compatibility: 1.15.2

Includes versions: 1.02.0 & 1.15.1

Corrections:

  • AGC 245 (no TB) Busbar LED indicator is ligthing up with the correct colors duw to the busbar state.
  • Improvements made in Digital AVR mode handling.
  • Idle Run Stop will now be started after Cool Down timer has expired.
  • DG allowed to take the load with any TB's with open fail in the section, if the DG nominal power is higher than the total PowerCapacity of TB's with openfail.
  • Available Power alarms are now cleared when a non PMS configuration is active.
  • Ground relay function will now use the scaling when selecting the biggest genset.
  • Release of crank relay (remove starter) improved to be done faster after set-point (rpm) is exceeded.
  • Phase sequence error are no longer detected when the voltage or frequency is outside volt/ frequency ok values.
  • Correction made to get Access Lock to block START and STOP buttons. 
  • Correction made in a system with more than one mains connection and one of the mains controllers have no TB, a GB synch fail could occur.
  • A Full Test is no longer terminated periodically, right after the BTB closes.
  • Some common PMS set-points are still working correct after a power cycle of all units.
  • Some power measurement view lines was not scaled when #9030 was changed. This has been corrected.
  • Auto start/stop OFF was not logged, when using M-Logic.
  • BLOCK mode introduced in MAINS controllers in 4.58.0 updated to secure backward compatibility to MAINS not having BLOCK mode. 

4.59.0

06.10.2016

PM compatibility: 1.15.1

Includes versions: 1.02.0 & 1.15.0.

New features:

  • Support of 3 x CIO-308 modules introduced

Changes:

  • CBE only active if an AVR-relay is selected or Digital AVR type DVC 310 or D510C is selected.

Corrections:

  • Correction of automatic starting and stopping gensets in power management setups.
  • M-Logic limit flags have now been added for the GB, MB, TB and BTB sync. failure alarms.
  • The slip-frequency comparison to sync parameters improved. Ensures that two equal frequencies can be synchronised together.
  • GB handling during load test updated.
  • Evaluation of inhibits parallel/not parallel updated to prevent wrong state when using compact breaker in single DG.
  • Corrected a scenario where cos phi droop would not work correctly.
  • MB handling updated in AUS mode when fail class trip MB/GB is active.
  • Mains LED handling corrected.
  • Corrected oil renewal function when running hours from EIC is used

4.58.0

15.07.2016

PM compatibility: 1.15.0

Includes versions: 1.02.0 & 1.14.6.

New features:

  • Support of new DEIF CIO modules CIO 116 and CIO 208.
  • BLOCK mode now available in MAINS.

Changes:

  • Active handling when returning from BLOCK is required when digital input or M-Logic is used to activate BLOCK.
  • Disabling of heavy consumer is possible.

Corrections:

  • DG could close onto a busbar with an MB position failure.
  • A mains now behaves correctly in AMF when #7065 “Start engine” is selected and the mains is the last healthy mains in a dynamic section.
  • Digital AVR bias is not sent if EIC control is disabled.
  • Text for menu 2614 changed to “Island ramp”.
  • Unreachable default setup of inhibts for some AC protections in BTB is corrected

4.57.0

06.07.2016

PM compatibility: 1.15.0

Includes versions: 1.02.0 & 1.14.6.

New features:

  • Support of ASC-4 added.
  • Selection of 'open MB when DG ready' added for 'SingleDG' to avoid 'MB open' if start failure is present. Channel 7065.
  • Possibility to change TSC1 source address for J1939 protocols added.
  • Selection of used frequency for alarm trip added. Channel 1204.
  • Hysteresis for mains detection (parameter 7090) added.

Changes:

  • DAVR Warning and DAVR Trip alarms are no longer inhibited by default, when the genset is not running.
  • Various default parameters optimised - especially for diverse regulators.
  • Phase sequence error alarms can now be disabled - only via USW.
  • Phase rotation setup available via M-Logic.
  • The evaluation of MBs is optimised to avoid blackout during change of BTB.
  • Activating 'Run my ID' only once via M-Logic added.

Corrections:

  • The evaluation of MBs is optimised to avoid total blackout during simultaneous mains failures.
  • State 'GEN-SET STOPPING' can no longer be terminated by changing from SEMI to AUTO.
  • Two new M-Logic flags for the Beckhoff alarms "CAN1 comm error" and "CAN2 comm error" have been added.
  • Missing return modes after test added.
  • Relay output configuration for IOM communication error now possible.
  • External stop is now logged in the event log.
  • CBE: At start failure on one DG the other DGs are now allowed to continue the CBE sequence even though the DG with failure is continuing its start attempts.
  • EIC measure alarms are now inhibited during EIC communication failure.
  • Idle run could cause external start not to work.
  • Improvements for M-Logic cooldown/stop threshold.
  • Beckhoff analogue input measure unit could go back to default during power cycle.
  • Running hour counter offset could be adjusted to more than 99999 hrs.
  • Nominal power for fixed power in 'SingleDG' is now following the selected nominal setting.
  • CBE breaker sequence GB+TB corrected (fault introduced in 4.55.0).
  • During sync-to-mains in single DG with overlap, the synchronisation could fail in rare situations.
  • Correction to dynamic M-Logic evaluation shown in USW.
  • Active LTO without backsync behaves correctly regarding breaker open/close during "Exclude from Run".
  • MTU ADEC module 501: “EIC Red lamp SD.” could occur unexpectedly. (Option H13).

4.55.1

20.04.2016

Corrections:

  • Engine communication issue which could restart unit is corrected.

4.55.0

30.11.2015

New features:

  • Setup of CAN pms due to Baud rate and number of units in plant implemented in jump menu 9170.
  • Hz/V OK timer for TB implemented in MAINS. Menu 6220 used for this purpose.
  • BTB NO/NC configurable via M-Logic. Overrules setup from plant application.
  • Direct BTB close on dead bus (A or B, A and B) implemented. Configurable via M-Logic.
  • Fast start of a section in ISLAND. Configurable via M-Logic.
  • EIC, MTU: 'Speed Demand Alarm' can be ignored. Configurable via M-Logic.
  • EIC, MTU: 'SS Override Alarm' can be ignored. Configurable via M-Logic.
  • 'Running Detection Reached' timer (parameter 6351) added.
  • 'External Engine Stop' detection (parameter 6352) added.
  • 'Frequency Detection Level' (parameter 6165) added.
  • Support of MAIN PCB version 3 added. Hardware info added in Service menu.

Changes:

  • Caterpillar, Basler CDVR update.
  • DM secondary log buffers have been updated.
  • Exhaust port temperature has been extended from 16 to 20.
  • DM1 log has been extended from 17 faults to 32 faults.
  • "MDEC Faults" alarms text has been updated for Option H13.
  • IDLE speed RPM is always sent regardless of parameter 2781.
  • DM2 request has been changed to broadcast mode.
  • Appl. hazard alarm extended with evaluation of number of units in plant. Information of wrong number of units stored in event log.
  • CBE: Voltage discharge timer made configurable in menu 2264 instead of being an internal timer with a fixed value of 5 seconds.

Corrections:

  • Initiated cool-down cannot be aborted when a wire break fail class alarm is present.
  • Idle run activation through digital input and reactivation after stop button function have been corrected.
  • Digital AVR communication alarm behavior during power up corrected.
  • Too early start by DGs when Mains units are switching to test mode is now avoided.
  • Positive/negative/zero sequence now able to handle short circuit and open conductors on all phases.
  • Phase sequence error is now detected and handled at both sides of the breakers (common alarm extended to two separate alarms in menu 2150).
  • Improvements made in short circuit limitation during load test (Option T1)
  • When powering up mains units, it is now prevented that ID to run is assigned before the Power Management is up and running.
  • Enabling and disabling of DVC (Digital AVR) transmission corrected.
  • Start of DGs in CBE now acting correctly with one mains and no TB or two mains with TBs in an AMF situation.
  • Status text for 'RAMP TO' enhanced.
  • Negative values in range -1.0 to 0.0 showed correctly in the display.
  • Missing return modes after test added in DG (parameter 7043) with power management activated.
  • Display performance enhanced.
  • Emulated TB power with MB open now calculated correctly.
  • Reading BTB status alarms (open/close/position) via Modbus corrected.
  • Service timer reset stored immediately.

4.52.1

20.04.2015

PM compatibility version 1.14.4
Includes version 1.14.3.

Corrections:

  • Positive and negative sequence measurements now working in phase rotation L1L3L2.
  • Test mode now saved, so the state is remembered during a power cycle.
  • Some analogue engine interface communication values added to delta analogue alarms.
  • When multi-inputs 46+47+48 are configured as binary, they are now shown in service menu under Digital input are.
  • Inhibit evaluation added to a number of AC alarms.
  • Scania EMS2 KWP2000 log clearing now possible.
  • Fan 3 hysteresis (parameter 6572) password level corrected.

4.52.0

04.03.2015

New features:

  • Ramp Speed 2 parameters added
  • Auto Ramp Speed Selection added
  • Droop active M-Logic events added
  • Ramp speed activation M-Logic commands added

Changes:

  • Q-droop limits are now ranging from -20000 to 20000.
  • All P/Q/Cosphi droop types will now use the present value at droop start as reference point of the droop
  • Scaling range 1 kV - 75 kV changed to 0.4 kV - 75 kV.

Corrections:

  • Start Enable input was able to block GB closing sequence in Power Management, if the input was deactivated while Hz/Volt OK timer was running.
  • Attempting to stop during idle at start, would ramp the engine to full speed and keep running, if the running detection speed had been reached during idle run.
  • GB could close on black busbar when another unit has position failure.
  • Solved missing deadband in peak shaving mode for percentage deadband.
  • Unit could reboot if a modbus command was sent while 'inhibit modbus commands' was active.
  • Secured mode does not work properly in LD start/stop situations
  • When a BTB was becoming present on the PM CAN line the generators could start up accidentally (and then close again without any other problems) - corrected.
  • Wrong scaling in frequency dependent power droop
  • The redundancy controller (option T1) was not acting completely as redundant controller in the power management setup. Issue introduced in version 4.51.0. Now corrected.
  • Counters1 area was too big to hold all the values.
    The consequence was that the read routine was setting all values to zero after each power cycle. Correction implemented + compiler checks of the areas added.
  • MB was able to open even though it was excluded from the LTO sequence - corrected.
  • In LTO, if the TB was tripped by the TB Trip failclass the MB was not able to close in all situations - corrected.
  • It is possible to select PM Primary and PM Secondary in channel 7841-42 (CAN prot. A and B) on AGC-232/233 variants. These two variants down not have PM.

4.51.0

03.03.2015

New features:

  • Double starter feature introduced in the AGC 200.
  • New busbar nominal selection added to make 'BB Unom = Gen Unom'. This gives 4 pairs of nominal generator/busbar voltage like AGC-3.

Changes:

  • It is possible to select inhibits in battery low/high (parameter 4950/4960/4970).
  • Minimum limit for Extended stop timer (parameter 6212) changed from 1 sec to 0 sec.
  • Maximum limit for Start attempts (parameter 6191) changed from 10 to 100.
  • DAVR updated to AGC-4 version 4.50.0 level.

Corrections:

  • Added support of ADEC CANopen, shutdown override.
  • No status text was shown when a GB was closed unexpectedly on a black busbar.
  • Parameters 1201 + 1202 are now fixed to Phase-Neutral, when not using Three-phase systems.
  • Fixed Power set point was previously reduced when the genset was derated.
  • Under AMF applications where a second mains fail occurs with at least one DG running, the remaining DGs are now started with a multi start.
    No PM backward compatibility is compromised due to this update.
  • Under AMF applications where a second mains fail occurs with at least one DG running and power cap overrule enabled, the timer is now reset (started over again) when DGs are ready and synchronised.
    No PM backward compatibility is compromised due to this update.
  • Multi stop now initiates the stop sequence for all DGs at once.
    No PM backward compatibility is compromised due to this update.
  • MTU MDEC 302/303 protocols battery voltage measurement corrected.
  • Start enable was required to be energised, if used, to activate the breakers - corrected.
  • Some translation texts were not used - texts now removed.
  • AGC Mains MB opens unwanted - corrected.
    No PM backward compatibility is compromised due to this update.
  • Parameter 3410 relay A setup corrected, so display shows correct value.
  • When LTO is activated with no Sync to mains; a delay is added to ensure that multimains status has been evaluated, before it is determined if MB should open.
    No PM backward compatibility is compromised due to this update.
    14-After MTU has released a new software for the SMART CONNECT module, the alarm "AL Speed Demand Failure" was always present due to a change in timeout changed from ~40m[s] ==> ~10m[s]
  • Power Management selection on CAN B was not initiated correctly - corrected.
    Application Configuration is not setting up the unit’s CAN bus lines any more.
    Select type of PM line in both the Application Configurations properties and in parameter 7840 as well.
  • Multimains MB fail control of 'Start engine' selection now used in AMF sequences.
    No PM backward compatibility is compromised due to this update.
  • Emulated voltage on busbar could occur, if GB was forced on and no engines were running.
  • DAVR start ramp was not working under CBE after cooldown.
  • If an LTO sequence was initiated while an auto switch was active, an MB could end up opening and closing in endless loop - corrected.
    No PM backward compatibility is compromised due to this update

4.23.1

18.07.2014

Information:

  • SW is reverted to version 4.32.1 due to problem with CAN B-line in version 4.42.0

4.42.0

10.06.2014

Note: This release require USW 3.38.0 or higher.

New features:

  • NEL groups implemented in M-Logic.
  • Fast LD start/stop timers added.
  • MTU ADEC module 501 communication (H13 option) introduced.
  • Under running feedback it is now possible to select running threshold (default 32 Hz) in parameter 6165.
  • Reset service timer command in M-Logic.
  • New alarm for indicating communication error to the IOM 2xx box implemented in parameter 7576.
  • Added Fuel fill check slope setpoint in parameter 6557.

Changes:

  • Parameter channel 1981 and 1983 added in M-Logic.
  • Oil renewal function made configurable. Output now possible to invert by using "Inverse proportional" checkbox in parameter 6890.
  • Oil renewal function got a new parameter (parameter 6893), where it is possible to set the Oil renewal timer reset threshold.
  • Added possibility to configure inhibits on the CanShare failure alarm.
  • Added Auto acknowledge possibility on CanShare failure alarm.
  • Option H8 parameter set point could reset if a power cycle was performed - corrected.
  • Parameter ranges in parameter 1150 and 1160 extended.
  • Increased parameter 2112 maximum value.
  • Hz/V Ok parameter 6821s minimum value now extended to zero.
  • Extended Fuel fill check timer (parameter 6553).
  • Made it possible to enable/disable Fuel fill check (parameter 6553).
  • Added several texts from the top line in the display to the USW Device page.
  • Made it possible to use Auto acknowledge on Ext. Comm. Error parameter.

Corrections:

  • AGC-4 and MTU ADEC(SAM) communication not started during certain power supply situations - corrected. (Updated correction to avoid start request after communication has been reestablished).
  • Removed dummy telegram from SCANIA.
  • Duplicate CAN ID alarm when configured for redundant controller/Critical Power Application could occur even if the controllers were OK - corrected.
  • AGC Not possible to complete LTO sequence in case Auto switch (parameter 8184) is active/ongoing - corrected.
  • AGC switch of plant mode (SEMI->AUTO) could have a temporary impact on the power reference - corrected.
  • AGC Incorrect information in power management related Modbus addresses - corrected.
  • AGC RMI fuel level measurement could be corrupted under power-up - corrected.
  • Regarding missing BTB close request from DGs corrected.
  • Regarding overflow in Q(P) protection.
  • Regarding Q sharing in asymmetrical load sharing on Group level corrected.
  • Regarding mix-up in whether phase/neutral or phase/phase measuring used for detection - corrected.
  • Relay error parameter 7600 could occur every time the unit was restarted even if it is acknowledged - corrected.
  • Regarding Idle Run start timer: Timer now resets if the Start Off timer is running.
  • Common AMF sequence in AGC could cause the assisting DGs to remain stopped even under an AMF situation - corrected.
  • Avoid unwanted TB opening - corrected
  • If the fourth current measure feature in channel 7005 is set to Multi Input transducer it will now only work in 4-20 mA Multi Input mode.
  • Voltages on Generator/Busbar in the Synchroscope view could be shown wrong - corrected.
  • Missing texts used in Input/Output panel in the USW now added.
  • Option H5/H13: Corrected missing alarm in MDEC 302 protocol.

4.23.1

12.11.2013

Corrections:

  • AGC 212/AGC 222/AGC 232/AGC 242 front foil: LED on the right side of the load arrow is now indicating voltage OK on busbar. In special Application configurations (Single DG
  • Application drawings with Mains present, except if the Genset mode, Ch 6070, is in Island Operation) it is indicating Mains OK/NOT OK.
  • "Live voltage detected" alarm in emulation mode will now occur, if voltage is detected on the AC measurement terminals.

4.23.0

28.10.2013

New features:

  • Identifier texts able to handle Uni-code strings.
  • AGC 245 and AGC 246: Menu 7005 extended with a separate selection of 3-phase CT mains power measurement. No backward compatibility is compromised due to this update.

Corrections:

  • AGC 245 and AGC 246: Mains power via 4th current input now calculated together with voltage on connector 61 instead of connector 68.
  • Log system extended so Event log, Alarm log and battery log are handling 150 entries.
  • Access lock updated: While Access lock is activated all the parameters and service information is able to be read.
  • Configuration of output relays corrected, so all functions can be connected to all available relays.
  • Selection of multi inputs for fuel pump logic corrected.
  • External IO: Analogue input scaling and unit are configured correct at startup and when changing the engineering unit.
  • Start sequence was interrupted almost immediately in emulation mode when doing CBE sequences. The reason was that nominal rpm was obtained instantly.

4.22.1

23.08.2013

  • Application emulation with breaker and engine commands inactive couldn't start the emulated genset properly.
  • DG not being under PMS control was still contributing to power summations used as basis for power reference calculations. PM backward compatibility is compromised due to this update in respect of taking DGs out of PMS control.
  • Endless start attempts when using CBE and rpm thresholds set to 0 rpm.
  • When synchronising BTB to external/unknown voltage source, the DGs online would not always react according to synchronisation command sent from the BTB. No PM backward compatibility is compromised due to this update.
  • M-Logic command "Start and Close GB" was ignored during cool down.
  • Idle run could elapse more than once during start sequence.
  • Command timer now able to activate even though unit is powered up in the middle of the period.
  • Application configuration for AGC 245 now drawn without the tie breaker as default.
  • Pushing hidden buttons results in event log entries.
  • Error in configuration of a parameter was causing the configured parameter to be hidden from the DEIF utility software parameter list. Error introduced in version 4.22.0, now removed.
  • "Mains sync. inhibit" accuracy on frequency threshold improved.

4.22.0

14.06.2013

Changes:

  • Ground relay: Update of the way the ground relay is activated; prioritising is now the power management priority number instead of the CAN ID.

Corrections:

  • Calibration of supply voltage measurement in production corrected.
  • PT sensor offset parameters now corrected to compensate for the cable resistance.
  • Power Management manual priority rearrange bug in the setup menu corrected

4.21.0

31.05.2013

New features:

  • Option "Emulation" introduced.
  • Functionality for limiting amount of nominal power allowed on busbar at a time due to limitations of short circuit current expanded to be included in the system logics of the DG and Mains. Until now it has only been supported by BTB units to determine whether connecting to sections was allowed. No PM backward compatibility is compromised due to this update.
  • Possibility of closing all BTB's in a ring-bus application added. No PM backward compatibility is compromised due to this update.
  • TB synchronisation will now be initiated in case the multi start forces start of too few DG(s) to get sufficient available power on busbar to meet the power reference. No PM backward compatibility is compromised due to this update.
  • 4 different voltage/power scalings introduced covering range from 10V/1.0kW up to 160kV/900.0MW. It is possible to have controllers using different scaling within a power management application. Controllers having PM compatibility version 1.00.0 or newer are able to understand if other controllers are using scaling even though they are unable to perform scaling themselves.
  • Separate settings for nominal busbar voltage introduced enabling synchronisation over step up/down transformers.
  • Menu 7054 in Mains unit for enabling common cos phi reference to DG(s) expanded. Possibility of making cos phi reference for DG(s) load dependent to hold fixed cos phi across MB added:
    a. Off (DG, Mains).
    b. Fixed for DG(s) (Mains).
    c. Fixed for imp/exp (Mains).
    d. Superior (DG).
    No PM backward compatibility is compromised.
    In fact DG(s) with older PM compatibility versions will be able to handle it if “Fixed for imp/exp” is selected in the Mains unit. “Superior” is the setting used for taking in cos phi reference from a unit placed at higher level in the system. If for instance DG(s) are to take in reference from a Mains unit, “Superior” must be selected in the DG(s).
    If DG(s) are to use their local reference the setting must be set to “Off”.
    In case “Fixed for imp/exp” is selected in a Mains unit it will seek to compensate for any DG(s) not being in “Superior” to maintain the requested cos phi across its MB. DG(s) with older PM compatibility version will behave as if “Superior” was selected and will therefore only use local reference in case no reference is received from the mains unit.
  • Load profiled running hour counter added.
    This counter is weighted with the percentage load of the DG.
    This counter is selectable as type of running hour on which to base DG priority in menu 8113:
    a. Total.
    b. Trip.
    c. Load profiled.
    Load profiled selection will not be compatible with units having older PM compatibility versions.
  • Priority handling updated.
    Now it is possible to make manual update of priorities in menu 8086 depending on either user defined priority order or according to running hours.
    a. Off.
    b. Manual update.
    c. Running hour update.
    This is independent of priority routine selected of the type selected in menu 8113.
    No PM backward compatibility is compromised due to this update.
  • Possibility of subtracting DG(s) from Power Management system added. It is now possible to select a Genset mode in menu 6071 other than “Power management” when being part of a Power Management application. When doing so normal operation of a SingleDG will be obtained.
    The DG(s) will no longer be available to the Power Management system.
    The Power Management communication itself will remain intact and no alarms will be introduced in the system.
    No PM backward compatibility is compromised due to this update.
  • Test in Island mode supported.
    Selecting TEST mode in a Mains unit being in Island mode will now result in execution of a test sequence.
    This is only true as long as either “Simple test” or “Full test” is selected as test type in menu 7044.
    If test type is set to “Load test” the TEST selection will be ignored.
    Units containing lower PM compatibility version will not be able to meet such Test request from the Mains unit.
  • Imax demand and Ithermal demand detection implemented.
  • Pulse counters implemented.
  • Oil renewal functionality implemented.
  • Additional analogue gov/avr offsets added. Now a unique set of offsets exists for each set of nominal parameters.
  • Derate function updated to support monitoring of three different input measurements instead of only one.
  • Additional energy counters added. Now separate set of counters exist for active and reactive energy both for export as well as import are available.
  • Command timers made accessible via display and made more start/stop dedicated. Backward compatibility is compromised.
  • M-Logic entries added for jumping to certain display views.
  • "Woodward SPM-D11" added as possible type of load-share units to interface to.
  • Support of Ground breaker feedback handling. No PM backward compatibility is compromised due to this update.
  • Five dedicated M-Logic alarms added.
  • View line informing about active regulators added.
  • Delta Analogue alarms 1-6 added.
  • Mains sync. inhibit functionality added.
  • Average U busbar high alarms added (menu 7480 + 7490).
  • M-Logic flag for acknowledgement of all AC mains protection alarms added.
  • Parameter modified support added.
  • Controller redundancy support added.
  • Breaker, engine and mains transformer names made part of identifiers.
  • Additional engine values supported in MDEC protocol.
  • RPM from engine communication can now be used in CBE sequence.
  • TB deload request added in M-Logic in SEMI-AUTO mode. In addition the 4th current input can be used for TB power. No PM backward compatibility is compromised due to this update.
  • Frequency and voltage droop regulation for DG implemented. Activated in M-Logic.
  • Read out of active fail classes on modbus address 1057.
  • Various existing functions added to use in or activate via M-Logic.
  • Ext analogue f/P reference and U/Q reference available via multi inputs. Configuration done via M-Logic.
  • Gov/AVR 5sec pulse from M-Logic now configurable in pulse length.
  • Force to CanShare from PMS functionality implemented (like analogue to PMS).
  • CanShare communication failure alarm implemented in menu 7860.

Changes:

  • Heavy consumer functionality optimised. PM backward compatibility is compromised in respect to heavy consumer handling.
  • U and Q low (1960 + 1970) alarms extended with two parameters (minimum current and phase angle) before the alarm can be activated when the voltage goes below the set point.
  • Various checks for BTB initialising close sequence bypassed in case BTB is configured as normally open and in Auto mode.
    No PM backward compatibility is compromised due to this update.

Corrections:

  • A normally closed Vac BTB being in AUTO and ready to close, but unable to do so due to missing BA and BB voltage, could block for other BTBs in the system to perform automatic closing.
    No backward compatibility is compromised due to this update.
  • Incorrect voltage reference would be used by DG(s) when synchronising a BTB against Mains connection(s). Phenomenon occurred when BTB was synchronising with DG(s) connected to busbar on one side and only Main(s) connected to the other.
    No backward compatibility is compromised due to this update.
  • Last 2 open BTB's in a ringbus application could both initiate synchronisation at the same time in SEMI auto and consequently close at the same time even though closed ring not allowed.
    No PM backward compatibility is compromised due to this update.
  • GB(s) could trip unexpected in applications with Mains without TB. Phenomenon could occur in case MB was performing back synchronisation and expirienced a MB close failure.
    No PM backward compatibility is compromised due to this update.
  • If doing LTO without sync to mains or AMF with "Start engine" MB would trip when DG volt/freq okay though the DG was performing initial Idle sequence. Not MB waits until DG is ready.
  • Correction to Idle sequence when Idle stop not used.

3.68.0

24.05.2013

Changes:

  • Ground relay: Update of the way the ground relay is activated; prioritising is now the power management priority number instead of the CAN ID.

Corrections:

  • Stop of DG during idle run secured even if idle stop is not enabled.
  • Idle speed could cause blackout in LTO and AMF when the DG starts. MB remains closed until DG is ready to take load (only when 7065 is configured to "Start engine").
  • GB(s) could trip unexpectedly in applications with Mains without TB. Phenomenon could occur in case MB was performing back synchronisation and experienced an MB close failure. No PM backward compatibility is compromised due to this update.
  • PT sensor offset parameters now corrected to compensate for the cable resistance.
  • Power management CAN B line disabled when switching from Standard application to Single DG application.

3.67.1

23.04.2013

PM compatibility version 1.01.5.

Includes versions: 1.01.4.

Corrections:

  • TCP/IP address distributed correctly in PM applications for reading in Connectivity check in USW.
  • OEM features corrected.

3.67.0

28.02.2013

PM compatibility version 1.01.5.
Includes versions: 1.01.4.

Changes:

  • In and Ie from fourth current measurement input can be configured in views.
  • OEM features updated.

Corrections:

  • Mains failure detection extended with evaluation of voltage phase angles.
  • The lower inhibit level for phase sequence error increased from 30% to 70% of nominal voltage.
  • Trip of MB and GB made faster due to fail class selections.
  • Shutdown override does not prevent transmission of stop command to ECU when fail class shutdown provoked.
  • Short circuit alarms (I>>) made faster and independent of voltage applied to inputs.
  • Scaling of analogue inputs on Beckhoff corrected.
  • Unexpected trip of GB in singleDG application when using overlap functionality.
  • Check synchronoscope view updated correctly when returning from log, parameter setup or service menu.
  • Mains power indication on SuperVision in Island mode of operation always displayed zero. No PM backward compatibility is compromised due to this update.
  • Energy counters day, week, month and service timer days stored correctly.
  • Incorrect M-Logic interpretation corrected.
  • Synchronising last open BTB located furthest to the right in a ringbus application could fail. In case Mains connected to busbar on its left side and DG(s) on its right side the DG(s) would not receive the command of performing synchronisation. No PM backward compatibility is compromised due to this update.
  • Capacity overrule did not work in case "Start engine" was selected and mains configured with MB and TB. No PM backward compatibility is compromised due to this update.
    CBE sequence updated so the excitation relay is kept energised throughout the cool down sequence in case voltage is present on the busbar.
  • VDO renamed to RMI (resistance measurement input).

3.66.1

11.02.2013

PM compatibility version 1.01.4.

Includes versions: 1.00.0, 1.00.1, 1.00.2, 1.00.3, 1.01.0, 1.01.1, 1.01.2 & 1.01.3.

Changes:

  • Power dependent Q import/export alarms modified to have separate parameter for VA reference.

Corrections:

  • Shifting between power management applications containing BTB(s) on the fly could fail. No PM Backward compatibility is compromised due to this update.
    General update of inverse time over current protections.(phase ( menu 1080), neutral (menu 1720) and earth (menu 1730)).
  • Power dependent PF droop curve improved. Slope set points changed
    from 2 decimals to 3 decimals (menu 7175 and menu 7176).
  • DG unit in power management is now able to send SEMI-AUTO
    command to MAINS unit in same section.
  • Load sharing with a Cummins PCC is now calculated correct.
  • Q reference used in power management in island operation when doing asymmetrical loadshare was incorrect. No PM Backward compatibility is compromised due to this update.
  • Resolution of TMS value for Inverse Current alarms changed from 1/10 to 1/100 for improved setup of trip curves. This influences the TMS values in alarm menus 1080+1720+1730.
  • Contrast level adjustment implemented in menu 9151. The setup is not available via USW interface.

3.65.1

15.08.2012

Corrections:

  • Mains power measurement calculation via multi input 46 corrected.
  • Modbus TCP/IP connection failed if master aborts the connection after few 100 us several times.

3.65.0

13.06.2012

New features:

  • View line containing power and Gen-L1N added.
  • PM hour priority available in measure view.

Corrections:

  • Volvo engine no longer starts up after end of battery test.
  • Configuration bits on parameters saved correct, when multiinput 47 or 48 configured as binary input.
  • Year max setting decreased to 2037 due to OS limitation.
  • Chinese translations shown correct in status menus in service menu.
  • Short circuit cut off level reduced from 40% to 2%.

3.64.1

23.04.2012

  • Running hours Absolute stored right after changes.
  • Swap timer in Fuel Optimization priority routine was not cleared properly.
  • EIC: MTU Smart Connect 'EIC faults' handled correct.

3.64.0

22.03.2012

New features:

  • OEM features extended.
  • "Clear Log" modbus command added.
  • Changes:
  • Logs cleared after firmware upgrade.

Corrections:

  • High frequency (above 350Hz) immunity on AC voltage input implemented.
  • Improved multi input setup handling during parameter file setup.
  • Language change 'on the fly' including more text updates.
  • EIC: Receiving single DM1 diagnostic not restricted in content any longer for all J1939 protocols.
  • Ground Relay updates: Hold Ground Relay active once V/Hz in range detected (avoids potential flickering). When bigger DG connects to busbar it deactivate/activated the ground relay once. When BTB deloading secure ground connection on both side of BTB. No PM Backward compatibility is compromised due to these updates.
  • Endless closing/opening of MB in a Multi-Mains application in case Overlap functionality enabled and a MB on a Mains is opened in LTO sequence which is not supposed to run. No PM Backward compatibility is compromised due to this update.
  • More robust TCP/IP connection with many (7-10) different instances connected at the same time. Max number is 10.
  • BTB position fail menus also available in unit.

3.63.0

09.02.2012

New features:

  • GOV and AVR signals can be inversed via analogue outputs via IOM. Use 'Inverse proportional' flag in menu 2781 (GOV) and 2782 (AVR).
  • Changes:
  • Changing language can be done without reboot/power cycling the AGC.
  • Ground Relay handling updated: Ground Relay activates as DG start up and remains activated until GB closed. Ground relay will open again in case GB closed and larger DG being on busbar and not preparing to disconnect the active Ground Relay. PM compatibility compromised in respect to GroundRelay functionality.
  • DG able to abort on-going stop sequence as long as extended stop sequence not yet initiated.

Corrections:

  • Modbus communication via TCP/IP is now allowed with slave id's in the range 1-255.
  • Ut3- Relay regulation now working correct with small differences (0,1Hz and 0,2Hz) between dfMax (ch 2021) and dfMin (ch 2022) for dynamic sync.
  • Textual clean up in protection menus.
  • If "DG missing" alarm was present as well as G3 option the unit would switch to analogue var-sharing. This is "old style" handling. Long time ago it was added as Mlogic entry to control when to force the use of analogue load-share. However it seems as the implementation at that time only updated this for kW-sharing.
  • Voltage level for analogue load-share where reset to 4.0V at every power up when "CumminsPCC" was selected.

3.62.0

23.12.2011

New features:

  • EIC: MTU J1939 Smart Connect supported.
  • EIC: After treatment / Diesel Particular Filtering implemented.
  • EIC: Digital AVR for Caterpillar CDVR implemented (option D1 required in combination with option H5).
  • EIC: Cummins PCC1301 supported for speed control.
  • EIC: Caterpillar (Perkins): Two DM1 logs available for support of ADEM (primary) and EMCP (secondary) at the same time.
  • EIC: Caterpillar (Perkins): Start/stop signal to ECU can be enabled/disabled via M-logic.
  • EIC: Speed control signal to ECU can be inhibited (enabled/disabled) via M-logic.
  • EIC: Volvo Penta ECM2.2 Fuel Disable supported for battery test.
  • EIC: Inhibit of EIC alarms can be setup via M-logic.
  • EIC: Standard AGC 200 Idlerun functionality now turns the engine to 700rpm on differents engines.
  • EIC: Protection lamp status and Malfunction lamp status implemented on J1939.
  • EIC: Both priority 3 and 6 are supported for Dash Display PGN, DM1 and DM2 logs.
  • EIC: Cummins: Shutdown override signal available.
  • EIC: Coolant level alarms (2 levels) implemented in menu 7670+7680.
  • Mini AOP LED's status available via modbus interface.

Changes:

  • EIC: Support of 19bit SPN numbers in DM1 and DM2 logs.
  • EIC: Occurrence counter available in DM1 and DM2 logs.
  • EIC: Engine hours available available up to 838000hours in display readout.
  • EIC: When changing nominal frequency, a ramp function will be performed.
  • Menu 2630: Auto acknowledge and inhibits flags available in USW.
  • Time gab from Multi-start demand occurs to Multi-start is executed diminished. Backward compatibility is not compromised due to this update.
  • Multi-start modified to achieve engines being started “simultaneously”. Backward compatibility is not compromised due to this update.
  • Close before excitation functionality modified to achieve close before excitation relays are energized “simultaneously”. Backward compatibility is not compromised due to this update.

Corrections:

  • OEM variant: Nominal RPM in menu 6010+6020+6030 not available.
  • Jump menu no longer in Service menu area since all parameters can be editted via the entire menu system.
  • OEM variant: FAN control is operational again.
  • Silence horn button pressed do not cause 'Acknowledge All Alarms' any longer. It does only reset the horn relay.
  • External IO handling is now able to obtain the correct modules during power up.
  • Use of GB/MB relays as configurable not causing an Relay Error alarm during power up when used as a function relay. This was only caused by a language different from MASTER/English language.
  • Correct handling of turning CAN off and on during shift of power management application from a single DG application to a Standard application.
  • A normally closed Vac BTB being in AUTO and ready to close, but unable to do so due to missing BA and BB voltage, could block for other BTB in the system to perform automatic closing. Backward compatibility is not compromised due to this update.
  • Incorrect voltage reference would be used by DG(s) when synchronizing a BTB against Mains connection(s). Phenomenon occurred when BTB was synchronizing with DG(s) connected to busbar on one side and only Main(s) connected to the other. Backward compatibility is not compromised due to this update.
  • Unwanted retrieval of command status by a unit powering up in a power management application. Backward compatibility is not compromised due to this update.
  • Correct indication of mounted hardware (use USW 3.31.0).

3.61.2

06.12.2011

New features:

  • None

Changes:

  • AC current cut off level decreased from 1.7 % to 1.0% of nominal current. Below 1.0 % will the current be set to 0 amps.

Corrections:

  • Detection of false Phase sequence error alarm and measurements during wire break of one or two AC voltage phases is corrected.
  • In very rare cases was some AC alarms too slow. Bug fixed.
  • Measurement view handling updated to prevent showing wrong text during power up

3.61.1

08.08.2011

  • Too long texts from translation in alarm list caused crash of alarm list. Length of texts now handled to ensure correct behavior of alarm list.
  • Missing parameters in ASW and USW added: 1340 BB Voltage Trip, 1390 BB freq Low 2 alarm and 1500 Unbalance Current alarm.

3.61.0

24.06.2011

New features:

  • Support Cummins PCC analogue loadsharing added via IOM 220/230.

Changes:

  • Menus (7000+7010) for power measurements on mains with external transducer available in AGC 212, AGC 213 and AGC 222.

Corrections:

  • Read out of ADEC value Mean Trip Fuel Consumption corrected, Coolant temperature, Fuel temperature and Charge air temperature now displayed with one decimal as for ADEC/MDEC for all J1939 protocols.
  • Termination of analogue load share Island Ramp in case of frequency increase.

3.60.0

06.06.2011

New features:

  • Support of Connectivity check of external connections (RS485 or TCP/IP). 
  • Used to verify if the external communications connected in a network is actually online or not (USW\SuperVision).
  • Support of Power Management Compatibility check.
    Used to verify if the power management functions are compatible between SW variants (USW\SuperVision).
  • Support of Genset Data display to be displayed in the USW\SuperVision. a. Compromises compatibility of Running Hour information amongst the controllers.
  • Preparation for scaling support to be introduced in upcoming AGC-4. Power management system now able to handle Step up/down transformers on busbar. a. MB, TB and BTB synchronization compromised. b. Power capacity check compromised. c. LD start/stop in apparent power compromised.
  • New Fail class "Trip MB/GB" added.
  • Normally energized alarm relay handling supported.
  • Normally de-energized breaker relay for MB continuous breaker handling added.
  • Possibility of obtaining infinite synchronization during static synchronization without giving breaker close commands added.
  • Power references possible to read out in views.
  • Power factor reference possible to read out in views.
  • Cosines Phi read out supported.
  • Power factor read out now reads out true power factor.
  • Low speed alarm added.
  • Aus mode supported in Mains and BTB units.

Changes:

  • Phase sequence error detection updated. Now the phase sequence error check is always performed on both side. The phase sequence detected is compared with the user defined expected/intended phase sequence.
  • BTB will wait for a period of time, equal to LD stop delay, before initiating its deload sequence during active operation.
  • MB is now able to perform black closing even though it is missing all units on the CAN line as long as TB is present and open.
  • Extended Stop is now executed whenever a Semi Stop command is given when the DG is at halt. This is despite the mode of the controller.
  • In Power Management application where “Update All” is selected, a controller being in Block mode will listen for the last mode update made in the system and return to that mode when leaving Block mode.
  • Service timer alarm now activates at 08.00 in the morning instead of 00.00 at night.

Corrections:

  • If TB was in the process of synchronising in Semi Auto mode, the sequence could not be aborted by a TB open command given via modbus.
  • If MB opens (trips) during LTO sequence before TB is synchronized and “SyncToMains” is enabled the TB do not connect DG(s) to load  as system expects synchronization to occur.
  • LTO sequence is active on IDToRun. Another Mains has MCU status and mode is shifted from SEMI to AUTO or vice versa on that Mains unit.  The LTO sequence is shortly interrupted – if BackSync ON MB is synchronized for ½s and then cancelled,  if BackSync OFF then TB is tripped (causing blackout) and MB closed and TB re-synchronized.
  • If common load present right of BTB and the Right Island was called upon from the left side,  the BTB would close before a DG managed to connect on the right side. If the other way around the BTB would wait until DG connected to the left and then synchronize and close.
  • If LD start/stop was done in percentage instead of in absolute value, the calculation to determine whether swapping of DGs due to priority order should be executed was invalid. The calculation secures that the swapping only takes place if the DG to be substituted is able to be stopped on LD stop condition after connecting the substituting DG.
  • A DG start threshold functionality already exists. It provides the possibility of adding a threshold value that a user defined input must  exceed before start sequence is initiated. The implantation was done in a way so the threshold value should be exceeded whereas just being  equal to was not sufficient. This gave complications if the threshold was to be done with just a digital input. Due to the general improvement
    of scaling handling this is now possible. As the digital input of the value “1” is compared to a one decimal threshold value any threshold
    value between 0.0 and 0.9 will now be seen as being below the value of the digital input.
  • NEL relays did not activate when application type was of the type "SingleDG".
  • If both ON and OFF feedback high on TB the MB would close without synchronization to voltage on busbar.
  • Control registers for enabling/disabling external control via constant commands instead of toggle commands added.
  • Transmit rate of speed telegrams (FF46 and TSC1) to EMS2 increased from 40ms to 20ms.
  • MMI updates regarding translate able texts and more space for alarm numbering in alarm list.

3.54.1

04.03.2011

  • AGC 222 supported.
  • Parameter 1560 “Neg. seq select” made independent of parameter 1590 “Zero seq select”.
  • Option H2 Modbus improved in multi drop configurations.
  • In BTB units was some fail classes not shown correct in USW and display. (Ch 1540, 1550, 1560, 1570, 1580, 1590, 1600, 1610, 1660 and 1700)”
  • RMS measurement improved. Before RMS measurement could be little outside Class 1 at a few frequencies. Measurement was all the time within Class 1 at 50 and 60 Hz.

3.53.1

07.12.2010

New features:

  • Subnet mask editable from display and make it possible to connect most typical networks.
  • MMI: Broadcast address is available in the display.
  • MMI: Menu 7513 added for RS485 bias selection.

Changes:

  • Menu 7561 IEC type = IOM as default and hereby makes the setup more easy.
  • A power cycle is not necessary naymore when the IP address is changed.
  • MMI: IP address is now displayed without extra ‘0’s.
  • Corrections:
  • PF was wrong if (P + Q) > 65535.
  • Df/dt calculation (Option A1) is updated for correct detection . Only relevant when number of measuring periods in parameter 1422 is set above 4.
  • MMI: Time Dependent Low Voltage Menu 1630+1640. Timer set point calculation for decimal resolution and setup of unit corrected.
  • MMI: Unit corrected to kV, if measure value is above 9999V.
  • MMI: Number of decimals corrected, when power factor is capacitive.
  • MMI: The first item in gateway address readout was IP address – now gateway address is shown.
  • External communication menu 7500 missing for option N (TCP modbus).
  • MMI: Menu 8110 Running hours is corrected.

3.53.0

25.10.2010

  • Ramping handling updated.
  • Load Take Over handling updated.
  • Type 212 and 213 supported.

3.52.1

23.07.2010

Heat foil control updated

3.52.0

06.07.2010

  • Earth current protection added.
  • Neutral current protection added.
  • FailClass "Safety Stop" updated.
  • Load depending start/stop handling updated.
  • BTB handling updated.
  • MB handling updated.
  • PM Communication handling updated.
  • Close Before Excitation functionality updated.
  • Language handling updated and full unicode implemented.
  • Heat foil control to sustain very low temperature. -40 degrees.
  • Type 243 added.
    Modeshift functionality updated

3.51.1

08.06.2010

Option H2 updated.

Auf dieser Seite können Sie Software-Updates für Ihr(e) Produkt(e) herunterladen und sich verschiedene Utility-Tools und Add-ons beschaffen, die Ihnen beim Einrichten und Konfigurieren Ihres Produkts/Ihrer Produkte sowie bei der entsprechenden Fehlersuche behilflich sein können.

Beachten Sie bitte, dass nicht alle unsere Produkte vom Benutzer aktualisiert werden können. Es werden auch nicht alle unsere Produkte mit einem Utility-Tool geliefert. Somit kann die Liste auf dieser Seite nicht als Übersicht unseres kompletten Produktsortiments angesehen werden.

DEIF registriert Ihren Download zusammen mit der verwendeten E-Mail-Adresse, um Ihnen auf Anfrage Informationen zu künftigen Updates zuzusenden.

DEIF kann nicht für die Folgen fehlgeschlagener Produkt-Updates oder die Nutzung von Utility-Tools haftbar gemacht werden. Auch haftet DEIF A/S nicht für die Folgen einer Verhaltensänderung von Produkten aufgrund eines Software-Upgrades. Es obliegt stets dem Anwender, vor der Inbetriebnahme die korrekte Einrichtung und Konfiguration sicherzustellen. Sehen Sie sich vor der Aktualisierung des Produkts das Versionsprotokoll der Software an.

Lizenzvereinbarung für den Software-Download von www.deif.com

Heruntergeladene Software bleibt Eigentum von DEIF. Die Software wurde möglicherweise nicht für gewerbliche Zwecke ausgegeben, sie wurde vollständig oder partiell geändert oder wiederverwendet oder sie wurde an jedwede Drittanbieter verkauft.Auf dieser Seite können Sie Software-Updates für Ihr(e) Produkt(e) herunterladen und sich verschiedene Utility-Tools und Add-ons beschaffen, die Ihnen beim Einrichten und Konfigurieren Ihres Produkts/Ihrer Produkte sowie bei der entsprechenden Fehlersuche behilflich sein können. 

Die aktuellste Version für volle Funktionalität

Wir empfehlen Ihnen, die von uns bereitgestellten Updates zu installieren, um so das volle Potenzial Ihres DEIF-Produkts nutzen zu können.

Die gesamte optimierte Software kann nach Belieben unter www.deif.com heruntergeladen werden. Navigieren Sie dazu zu „Software“ und dann zu „Software-Download“.

Bei Fragen oder Problemen beim Auffinden der entsprechenden Software für Ihr Produkt wenden Sie sich telefonisch unter der Rufnummer +45 96149614 an DEIF A/S oder an die jeweilige lokale DEIF-Niederlassung. Alternativ können Sie uns auch eine E-Mail an support@deif.com senden. Wir helfen Ihnen gerne weiter.