1.02.1

Changes:

  • When M-Logic cooldown threshold is selected, it will be used regardless if parameter 6214 is 0.
  • Improved RPM measurement.

Corrections:

  • EIC alarms used as low alarms would appear when the CAN communication was lost.
  • Idle run could cause external start not to work.
  • Running hour counter offset could be adjusted to more than 99999 hrs.
  • Engine could end up in an infinite state between crank and running detection.
  • Alarms added to prevent this:
    - Running detection reached timer (parameter 6351)
    - External engine stop detection (parameter 6352)

1.02.1

15.03.2016

Changes:

  • When M-Logic cooldown threshold is selected, it will be used regardless if parameter 6214 is 0.
  • Improved RPM measurement.

Corrections:

  • EIC alarms used as low alarms would appear when the CAN communication was lost.
  • Idle run could cause external start not to work.
  • Running hour counter offset could be adjusted to more than 99999 hrs.
  • Engine could end up in an infinite state between crank and running detection.
  • Alarms added to prevent this:
    - Running detection reached timer (parameter 6351)
    - External engine stop detection (parameter 6352)

1.02.0

03.02.2016

New features:

  • Contrast offset added in parameter 9152.
  • PT 1000 sensors introduced in multi-input 6 and multi-input 7.
  • Several events and limits added to M-Logic.
  • Added one additional battery low alarm (parameter 4950).
  • Inhibits can be set in battery low/high menu (parameter 4950/4960/4970).
  • Oil renewal feature introduced.
  • Battery voltage column now available in every entry in the log information in the DEIF Utility Software.
  • Added three freely translatable texts in the view lines.
  • Added support of ADEC CAN open, shutdown override.
  • Added EIC manual speed regulation

 

Changes:

  • Multi-inputs made linear in application emulation.
  • Extended maximum limit in start on time, parameter 6183.
  • Extended fuel fill check timer (parameter 6553).
  • Made it possible to enable/disable fuel fill check (parameter 6553).
  • Made it possible to use auto acknowledge on Ext. Comm. Error parameter.
  • Start attempt maximum limits changed. Extended stop timer minimum limit changed.
  • Language translation changed. From now on it is not possible to select a different font. The two fonts are now merged together, and containing all previously used characters. New characters are added. If any unsupported signs are written to the device, the signs will appear as ' ' (space).
  • Three RMI sensor curves added. One for each RMI type.  It will be possible to choose them in channel 10460, 10630 and 10800 by selecting "Sensor type 4" in the DEIF Multi-line 2 Utility Software v.3.

Corrections:

 

  • Stop coil did not activate when start sequence was aborted.
  • Corrected missing digit to running hours.
  • Sign of display values between -1.0...0.0 with one or two decimals shown correct.
  • Missing EIC values in analogue delta alarms added.
  • Measurement through the MPU input caused periodical peaks in the RPM measurement,  which could cause an unwanted trip of the generator breaker.
  • M-Logic line combination misinterpretation corrected.
  • Application emulation couldn't start properly with breaker and engine commands selected as inactive.
  • PT sensor offset parameters now corrected to compensate for the cable resistance.
  • Unit and MTU ADEC(SAM) communication not started during certain power supply situations - corrected. (Updated correction to avoid start request after communication has been reestablished).
  • M-Logic command "Start and Close GB" was ignored during cool down.
  • SCANIA EMS2 correction of start/stop.
  • Clock synchronise over Modbus was causing the service timer to offset its current timer value - corrected.
  • Configuration of output relays corrected, so all functions can be connected to all available relays.
  • Selection of multi-inputs for fuel pump logic corrected.
  • Fuel pump relay could activate at power-up of the controller before fuel level measurement has settled.
  • Several Modbus (option H2) addresses were not working - corrected.
  • MTU MDEC 302/303 protocols battery voltage measurement corrected.
  • Idle run timer now resets at each start attempt.
  • Nominal RPM now available to configure.
  • Hz/V failure group 4560 is removed.
  • Unit could reboot if a Modbus command was sent while 'Inhibit modbus commands' was active
  • Running hour counter could reset unintendedly - corrected.
  • Running hour counter could reset unintendedly at power cycle - corrected.
  • Scania EMS2 KWP2000 log clear now possible.
  • Exhaust gas temperature - right/left was not shown correctly in display.
  • Storage of service timer values during reset corrected.
  • Relays could activate under boot sequence - corrected.

1.01.0

23.02.2015

New features:

  • Common alarm
  • Siren

Changes:

  • Relay 3 default setting changed from Horn to Not used

Corrections:

  • The functionality of not showing alarm in case of combination of the alarms used in relays has been corrected
  • Idle run activation through digital input and reactivation after stop button functions have been corrected
  • Idle run function corrected

1.00.2

01.09.2014

Corrections:

  • Relay channel error after power up corrected
  • Parameter 3410 password corrected
  • MTU Smart Connect engine protocol updated

1.00.1

26.11.2013

Corrections:

  • Day of week is not adjusted when the date is changed - Corrected
  • Several menu texts were not using translations - Corrected
  • CU 100 (GCU 111 + 112): Not able to start on D.I Remote Start - Corrected

1.00.0

01.05.2013

  • First release

Auf dieser Seite können Sie Software-Updates für Ihr(e) Produkt(e) herunterladen und sich verschiedene Utility-Tools und Add-ons beschaffen, die Ihnen beim Einrichten und Konfigurieren Ihres Produkts/Ihrer Produkte sowie bei der entsprechenden Fehlersuche behilflich sein können.

Beachten Sie bitte, dass nicht alle unsere Produkte vom Benutzer aktualisiert werden können. Es werden auch nicht alle unsere Produkte mit einem Utility-Tool geliefert. Somit kann die Liste auf dieser Seite nicht als Übersicht unseres kompletten Produktsortiments angesehen werden.

DEIF registriert Ihren Download zusammen mit der verwendeten E-Mail-Adresse, um Ihnen auf Anfrage Informationen zu künftigen Updates zuzusenden.

DEIF kann nicht für die Folgen fehlgeschlagener Produkt-Updates oder die Nutzung von Utility-Tools haftbar gemacht werden. Auch haftet DEIF A/S nicht für die Folgen einer Verhaltensänderung von Produkten aufgrund eines Software-Upgrades. Es obliegt stets dem Anwender, vor der Inbetriebnahme die korrekte Einrichtung und Konfiguration sicherzustellen. Sehen Sie sich vor der Aktualisierung des Produkts das Versionsprotokoll der Software an.

Lizenzvereinbarung für den Software-Download von www.deif.com

Heruntergeladene Software bleibt Eigentum von DEIF. Die Software wurde möglicherweise nicht für gewerbliche Zwecke ausgegeben, sie wurde vollständig oder partiell geändert oder wiederverwendet oder sie wurde an jedwede Drittanbieter verkauft.Auf dieser Seite können Sie Software-Updates für Ihr(e) Produkt(e) herunterladen und sich verschiedene Utility-Tools und Add-ons beschaffen, die Ihnen beim Einrichten und Konfigurieren Ihres Produkts/Ihrer Produkte sowie bei der entsprechenden Fehlersuche behilflich sein können. 

Die aktuellste Version für volle Funktionalität

Wir empfehlen Ihnen, die von uns bereitgestellten Updates zu installieren, um so das volle Potenzial Ihres DEIF-Produkts nutzen zu können.

Die gesamte optimierte Software kann nach Belieben unter www.deif.com heruntergeladen werden. Navigieren Sie dazu zu „Software“ und dann zu „Software-Download“.

Bei Fragen oder Problemen beim Auffinden der entsprechenden Software für Ihr Produkt wenden Sie sich telefonisch unter der Rufnummer +45 96149614 an DEIF A/S oder an die jeweilige lokale DEIF-Niederlassung. Alternativ können Sie uns auch eine E-Mail an support@deif.com senden. Wir helfen Ihnen gerne weiter.